ICT Encapsulated Interposing current transformer Isolated current transformer CP-4 series for protection

YUEQING HEYI ELECTRICAL CO,LTD
Contact Now

ICT Encapsulated Interposing current transformer Isolated current transformer CP-4 series for protection

  • 1
  • 2

Brand Name : HEYI

Model Number : ICT

Place of Origin : CHINA

MOQ : 1 PCS

Price : USD 1-20/pcs

Payment Terms : L/C, T/T, Western Union, D/A, D/P, MoneyGram

Supply Ability : 100000 Piece/Pieces per Month

Delivery Time : 1-5 days

Packaging Details : Standard Export Carton

Accuracy class : 0.5/1.0

Coil Structure : TOROIDAL

COLOR : Black

Normal secondary winding : 1A or 5A

Operating voltage : 0.72kV

Contact Now

Encapsulated current transformer

Tough resilient flame retardant UL-94V0

Temperature range: -20°C to 70°°C

Accuracy class: 1.0, 0.5

Test voltage: 4kV 50Hz 1min

IEC44-1,IEC185,BS3938,DIN42600

Insulation Class E, Max 120°C

Totally enclosed in tough,self extinguishing mouldings

Operating voltage: 0.72kV

Summation current transformer

Normal secondary winding: 1A or 5A

Compliance:IEC 185 and BS 3938/1973

Burden:5VA or 7.5VA

Accuracy:0.5 or 1.0

Rated voltage:720V 50/60Hz

Dielectric voltage:4kV

Type of material:High impact flame-retardant moulded resin

Input:5/5A,1/1A other by request.

FAQ:

A. When the main C.T.s having rated secondary current of 1Amp.And the burden requires a rated current of 5Amp,an I.C.T.is used,at the load end so that the lead burden is fed by 1Amp.Current.The lead burden on the I.C.T.is negligible as it placed very close to the burden(Pic.1).

B. The arrangement suggested in a above may also be used when the main C.T.is having rated secondary of 5Amps.And the burden requires a rated current of 1amp.In this case .However,the I.CT, of ratio 5/1 Amp will have to be placed at the main C.T.end to reduce the effect of lead burden on the main C.T.(Pic. 2)

C. In the case of transformer differential protection when the main C.T. ratios do not match.If phase shift is introduced due to the model of connections of the transformer on the H.T. and L.T.side,I.C. Ts Can be used to correct the phase shift.It is assumed here that all main C.Ts are star connected(Pic.3)

D. For suppressing zero sequence currents from the out of balance current.This is achieved by providing an additional secondary winding on I.C.Ts.Which is connected in closed delta(Pic.4)

E. If high ratio is selected for the main C.T. against a low load current,I.C.Ts may be used across the main C.T. to reduce the ratio effectively and satisfactorily cater ti the rated current requirement of the burden(Pic.5)

In all above applications it must be borne in mind that an I.C.T. imposes burden on the main C.T.if this burden is required to be restricted to a certain value,the value must be specific to enable the manufacture to design the I.C.T.suitably.If this value of burden(expressed in VA)is too low,it may result into an uneconomical design of the I.C.T.

ICT Encapsulated Interposing current transformer Isolated current transformer CP-4 series for protection


Quality ICT Encapsulated Interposing current transformer Isolated current transformer CP-4 series for protection for sale

ICT Encapsulated Interposing current transformer Isolated current transformer CP-4 series for protection Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: YUEQING HEYI ELECTRICAL CO,LTD
*Subject:
*Message:
Characters Remaining: (0/3000)